| ID | Run | Size | Notes |
|---|---|---|---|
| P1 | House battery + → house Class-T, battery side | 2 AWG | Straight up from the battery onto the shelf |
| P2 | House Class-T load → house 100 A breaker | 2 AWG | Inches — straight up, the breaker stacked directly above its own Class-T. 🔑 100 A, and the number is not arbitrary: it protects the 8377's BUSES, which are rated 100 A. Nothing else does — a 200 A Class-T sits upstream, so without this breaker a bus-level fault has no device sized to it. That is the whole reason the breaker exists, and it is why this one must not be quietly upsized to match the start side |
| P3 | Start battery + → start Class-T, battery side | 2 AWG | |
| P4 | Start Class-T load → start 150 A breaker | 2 AWG | Same arrangement. 🔑 150 A here, because this is the only breaker in the crank path: cranking at ~100 A sits at 67 % of rating, and the breakaway peak is over in tens of milliseconds — far too fast for a bimetal to see |
| P5 | 6011 LOAD-2 → starter solenoid | 2 AWG | Crank positive, out of the switch and straight aft to the solenoid — not via a stud, because that is the switch's whole job. This is what makes cranking switchable. It still crosses the bulkhead, but through a grommet |
| P6 | Lug plate HOUSE + → house Class-T load | 2 AWG | ≈ 6 ft measured. 75 mV at 80 A. The only cable still running the full distance |
| P7 | Start Class-T load → 2204 stud | 2 AWG | 🔑 The shared unswitched run. Alternator and start charger both hang off the far end of it, so this one cable replaces what used to be two long ones |
| P8 | 2204 stud → alternator B+ | 2 AWG | Short jumper into the blind zone, made on the bench. 🔴 DELIBERATELY UNFUSED — a fuse in an alternator lead is itself a load-dump mechanism |
| P9 | 2204 stud → lug plate START + | 2 AWG | Short jumper. The start charger's own fuse sits at the charger end, on its 8 AWG pigtail |
| P10 | House breaker INPUT side → fused positive busbar (unswitched) | 8 AWG, 5006100 + 40 A MAXI at source | Feeds bilge · Cerbo · GX LTE · shunt sense. 🔑 Shares the breaker's AFT terminal with P2 — upstream of the trip mechanism, so it survives the master switch and a breaker trip, which is the whole point of it, while leaving the Class-T load stud at two conductors. ⚠️ The simpler route was considered and rejected on purpose: taking it straight off 6011 BAT-1 would be tidier, and it would go dark the moment the house breaker tripped. Do not "simplify" it back. Sized for a ceiling of ~40 A if a second bilge pump ever lands on that bus; realistic load is ~11 A. 10 AWG would do, 8 AWG has margin and is on hand. 🔴 It needs its own fuse at the source — see the assumptions |
| P11 | House 100 A breaker → 6011 BAT-1 | 2 AWG | Shelf up to the panel |
| P12 | Start 150 A breaker → 6011 BAT-2 | 2 AWG | Shelf up to the panel |
| — | 6011 LOAD-1 → the 8377 | 2 AWG | Panel-internal, and unbroken: the protection sits upstream on the two 150 A breakers, so there is no breaker in this leg |
| N1 | House battery − → SmartShunt, BATTERY side | 2 AWG | 🔴 The only cable on that post. About 1.5 ft as drawn |
| N2 | Start battery − → SmartShunt SYSTEM side | 2 AWG | Start current never crosses the shunt |
| N3 | SmartShunt SYSTEM → panel negative busbar | 2 AWG | The single negative arriving at the panel |
| N4 | Engine block ground → 2203 stud | 2 AWG | Short jumper, made on the bench, fitted once. 🔴 Block landing point unconfirmed |
| N5 | 2203 stud → start battery − post | 2 AWG | 🔑 The mirror of P7 — one shared run doing two jobs, carrying the crank return and the chargers' common return together. Lands on the battery post, not the panel and not the shunt, which keeps the crank loop at 16 ft and the start post at two conductors |
| N6 | Lug plate common − → 2203 stud | 2 AWG | Short jumper. ❌ This used to be drawn running the full 6 ft to the shunt — wrong. It terminates at the stud like everything else on that side, and reaches the shunt through N5 |
| B1 | Panel → bilge pump + float, port aft | 14 AWG | 10 A fuse. Unswitched |
Everything the drawing rests on that has not been measured twice. Each of these gets confirmed aboard before anything is cut.